UPS 400KVA model DPS-400K
Mô tả
DPS Series, Three Phase UPS 400KVA
Ultimate Availability
• Supports up to 9.6 MW power capacity with the parallel redundancy and expansion up to 8 units
• Redundancy components and dual CAN bus ensures system availability
• Proactive detection of key component status for early diagnosis on UPS malfunction
• Intelligent battery health diagnosis enables better battery maintenance and replacement
• Advanced event analysis, including 10, 000 event logs, waveform capturing and key parameters recording, to detect UPS abnormality and ensure higher availability
Excellent Performance
• The industry’s leading power density and smallest footprint with the design of both top/ bottom cable entry* and inbuilt switches (* For DPS-400K, only top cable entry is available)
• Unity output power factor guarantees no-rating and provides 100% kW
• AC-AC efficiency of up to 96.5% and 99% in ECO mode resulting in marked energy cost savings
• Supports both VRLA and environment-friendly Li-ion batteries
Sophisticated Manageability and Flexibility
• User-friendly 10” color touch panel simplifies local UPS management
• Environment information, such as security, water, fire, and temperature can be integrated and monitored via the LCD panel of the UPS
• If the UPS is equipped with an external battery management system, the battery information can be integrated and monitored via the LCD panel of the UPS
• Fully front access and modular design of key components shortens the mean time to repair (MTTR)
• Flexible battery quantity of 30-46 pcs achieves optimal battery investment
DPS Series, Three Phase UPS 400KVA |
||
Technical Specification | ||
Model | DPS-400K | |
Power Rating | kVA | 400 |
kW | 400 | |
Input | Nominal Voltage | 220/380Vac, 230/400Vac, 240/415Vac (3-phase, 4-wire + G) |
Voltage Range | 176/304~276/478Vac (full load) | |
Current Harmonic Distortion | < 3% (with Full Linear Load); < 5% (with Full Non-linear Load) | |
Power Factor | > 0.99 | |
Frequency Range | 40~70Hz | |
Output | Voltage | 220/380Vac, 230/400Vac, 240/415Vac (3-phase, 4-wire + G) |
Voltage Harmonic Distortion | <1.5% (Linear Load); < 5% (Non-linear Load) | |
Voltage Regulation | ±1 (static); ±5 (dynamic) | |
Output Power Factor | 1 | |
Frequency | 50/60Hz (Auto-Selectable) | |
Overload Capability | ≦ 125%: 10min ; ≦ 150%: 1min ; > 150%: 1sec | |
Display | 10” Color Touch Panel | |
Interface SNMP card inbuilt in touch screen | Standard | RS232, Parallel port, USB, Modbus RS485, Input dry contact, Output dry contact, |
Optional | Relay I/O card, Battery cabinet temperature sensor cable | |
Conformance | Safety | CE |
Efficiency | AC-AC Mode | Up to 96.5% |
ECO Mode | 99% | |
Battery | Type | VRLA, LiB |
Charge Current | 120A | |
Battery Quantity | 30~46pcs | |
Environment | Operating Temperature | 0 – 40℃ |
Relative Humidity | 0~95% (non-condensing) | |
Audible Noise | < 80dB | |
IP Protection | IP 20 | |
Others | Parallel Redundancy and Expansion | Maximum 8 units |
Emergency Power Off | Remote and local | |
Physical | Dimensions (W x D x H) | 1200 x 900 x 2000mm |
Weight | 700kg | |
* The width is for the cabinet which has four inbuilt switches. | ||
All specifications are subject to change without prior notice. | ||
DPS series 400kVA is highly integrated with four built-in switches as standard model |
Hãy đặt nền móng cho sự hợp tác bằng cách gọi cho tôi
(Mr Hoàng) Hotline: 0388454589
Website: Dieuhoachinhxac.com
Đánh giá
Chưa có đánh giá nào.