Ups delta 2kva
UPS Input: The UPS system input shall be configurable as single powered from a L/N/G Single phase source. Power input cord cable is standard with UPS.
1. Input nominal AC voltage: 220V or 230V or 240V. Line + neutral + ground.
2. Input AC voltage range: 175 – 280V at 100% load, 80 – 175V at 50% ~ 100 % load linear de-ration.
3. Input current: 2kVA: 220V: 9.4A, 230V: 9.0A, 240V: 8.6A.
4. Input frequency range: 50/60 ± 10Hz Auto selectable.
5. Input Power Factor: > 0.99 @ 100% load
6. Input current distortion THDi: < 3% @ 100% load
7. Input Power with fully charged battery and 100% load: 2kVA: 1961W.
8. Input protection: 2kVA: 20A Breaker 1 Pole
9. Short circuit capability: 6 times of rated current, 0.1~1.8sec
UPS Output Ups delta 2kva:
1. Output nominal AC voltage: 220V or 230V or 240V, Line + neutral + ground.
2. Output nominal current: 2kVA: 220V: 9.1A, 230V: 8.7A, 240V: 8.3A.
3. Output THDv%: a) < 3% for linear load. b) < 5% for non-linear load.
4. Output AC voltage regulation: a) ± 2% for linear load. b) ± 3% for non-linear load.
5. Transient response: ±10% for 10 – 90% load variations.
6. Transient response recovery time: < 80ms.
7. Output nominal frequency: Auto selectable frequency 50 or 60Hz.
8. Output frequency stability: a) ± 0.1Hz. b) ± 1% with mains synchronize.
9. Slew rate: < 1Hz/sec.
10. Overload Rating: (± 2%): a) < 105% continuous. b) 105%~125% for 1 minute. c) 125%~150% for 30 seconds. d) ≥ 150% for 0.5 second.
11. Inverter short circuit capability: 2kVA: < 35A, 4~5.cycles
12. Crest factor: 3:1
13. System AC-AC Efficiency: 2kVA: 93%.
14. Output power factor: 0.9
2.3.4 Bypass :
1. Bypass AC voltage range: ± 5%~15% adjustable.
2. Bypass frequency range: 50/60Hz Auto selectable, ± 5Hz adjustable